Intelligent, Networked, Multi-Channel Fire Alarm Control
and Emergency Voice Evacuation System Description
The E3 Series™ Broadband System includes the Net-
SOLO™ Broadband System. Like the NetSOLO™ Broad-
band System, the E3 Series™ Broadband is of modular
design and allows a wide range of configurations from two
basic assemblies. These assemblies form an integrated,
distributed fire alarm system that includes audio evacua-
tion and fire command capability. The network communica-
tion transmits all fire alarm, audio evacuation, voice paging,
and fire fighter communications.
E3 Series™ Broadband is a revolutionary advance in fire
detection and emergency voice evacuation system design.
E3™ Series Broadband employs proven technology and
expands it to accomplish emergency multi-channel voice
evacuation, two-way fire fighter communications, and
building control applications, all over a single pair of wires
or fiber-optic cable.
It is a true peer-to-peer, token ring passing, networked sys-
tem capable of supporting up to sixty-four (64), individual
nodes. All system status, control-by-event sequences,
audio voice paging, and fire fighter telephone signals are
sent between nodes over a single pair of wires or fiber optic
cable.
Each E3 Series™ Broadband node can be spaced along
the network a maximum distance of 3,000 feet (914.4 m)
over an unshielded twisted-pair of wires or fiber-optic cable
with up to 8dB loss. Built-in isolation at each node permits
Style 4, 6, and 7 network configurations.
E3 Series™ Broadband is simple to configure for any
project requirement. A complete E3 Series™ Broadband
application can be assembled from just three types of
nodes; the 7100 NetSOLO, the INCC Command Center,
and the INX Transponder.
E3 Series™ Broadband is capable of the most sophisti-
cated sequences of operations.
E3 Series™ and NetSOLO™ are trademarks of Honeywell International Inc.
Features
• Listed under UL Standard 864, 9th Edition.
• UL Listed for smoke control when properly configured.
• All communication signals and control-by-event
sequences over a single pair of twisted, unshielded
wires or fiber-optic cable.
• Distributed architecture, including Style 7 wiring configu-
rations, allow system components to continue normal
operation with no loss of function during single line fault
conditions.
• Integrates INX transponders and INCC command cen-
ters to create a complete audio evacuation system with
up to sixty-four (64) nodes.
• Redundant command centers with microphone and fire
fighter’s handset easily configured by adding INCCs.
• State-of-the-art digital signal processor (DSP) technol-
ogy for efficient audio compression and filtering.
• Up to 150 watts of audio power from three (3), AM-50
amplifiers with an additional 50 watts of standby power
in each intelligent network transponder (INX) cabinet.
APPROVED
FM
MEA Approved
SIGNALING
City of
Chicago
Approved
City of
Denver
Approved S1869 3025415 231-06-E 7165-0694:268
7165-0694:269
Class 1
Class 2
High Rise
An ISO 9000-2000 Company
E3 BroadbandGAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9020-0613 Rev. C   page 2 of 5 www.gamewell-fci.com
The Field Configuration Program (FCP) is based on Bool-
ean logic statements providing AND, OR, NOT, and XOR
logic operators. These can be combined to produce addi-
tional Boolean operators such as NAND, NOR, XNOR, etc.
system silence, etc. The E3 Series™ Broadband is soft-
ware-programmable for multi-channel digital audio applica-
tions. It is ideal for a wide range of complex system
applications including high-rise or campus installations. An
array of cabinets allows for neat, compact, attractive instal-
lations.
A comprehensive set of timing functions can also be
attached to any input/output logic statement for staggered
reset of fan control relays, time-delayed alarm activation,
automatic.
The E3 is a microprocessor-based fire alarm control panel
that uses an ILI-MB-E3 Intelligent Loop Module with two (2)
signaling line circuits and two (2) notification appliance cir-
cuits. When transmitting to remote locations, the optional
RPT-E3 provides the ILI-MB-E3 with signal boosting and
transient protection, as well as connectivity for both wire
and fiber-optic cables. Options also include an integral Dig-
ital Alarm Communicator Transmitter (DACT) supporting
most popular reporting formats.
The Intelligent Network Command Center (INCC) serves
as the point of interface between an operator and the sys-
tem’s audio evacuation, fire fighter intercom, and building
network. The INCC occupies a single address on the E3
Series™ Broadband network. A typical INCC assembly
consists of an Intelligent Network Interface-Voice Gateway
(INI-VGC-FO or INI-VGC-UTP) module (fiber-optic or
unshielded twisted-pair), or INI-VGC-UTP (unshielded
twisted-pair only), one or more Addressable Switch Mod-
ules (ASM-16), optional Network Graphic Annunciator
(NGA) and remote 48 LED driver module (ANU-48).
Options include a paging microphone and a fire fighter’s
handset connecting to the INI-VGC-FO or INI-VGC-UTP.
Each INI-VGC can support up to sixteen (16), ASM-16
modules. Each ASM-16 has sixteen (16), push-button
switches for a maximum capacity of 256 switches per  INI-
VGC command center. Each switch has three (3), associ-
ated LEDs, colored green, yellow, and red. These switches
and their LEDs are fully programmable to serve any sys-
tem function desired. They can control audio speaker cir-
cuits, notification appliance circuits, addressable relay
outputs, fire fighter phone control circuits, or any special
application that might be required.
Multiple INCCs can be configured into the E3 Series™
Broadband network to serve as a completely independent
command center for their local area or as remote com-
mand centers mimicking, in part or in whole, the function of
a main command center.
The Intelligent Network Transponder (INX) acts as
a network audio transponder for the E3 Series™ Broad-
band Network. The INX transponder serves as the point of
distribution for the system’s audio and fire fighter telephone
circuits and occupies a single node on the E3 Series™
Broadband network.
A typical INX assembly consists of an ILI-MB-E3 or
ILI-S-E3, an Intelligent Network Interface-Voice Gateway
(INI-VGX) module, a PM-9 power supply, and up to four
(4), AM-50 amplifiers. The INX transponder occupies a sin-
gle address on the network and provides termination points
for the network connection using either a pair of unshielded
twisted-pair wire or fiber-optic cable.
The INI-VGX uses advanced Digital Signal Processing
(DSP) technology for audio compression and filtering
allowing E3 Series™ Broadband to produce the clearest
audio possible while conserving network bandwidth for
instantaneous response. Background noise is automati-
cally filtered during voice paging and fire fighter communi-
cations increasing audibility and eliminating the need for
push-to-talk devices.
The INI-VGX can accommodate up to sixteen (16), differ-
ent messages with a total combined duration of three min-
utes. Each message can be field installed via a laptop
computer and can be in the form of a voice message or an
evacuation tone.
The INI-VGX also provides a fire fighter phone riser and an
addressable signaling line circuit connecting to multiple
phone jacks or warden stations through as many as sixteen
(16), AOM-TELF modules. In addition, the INI-VGX SLC
can support up to thirty-two (32), speaker circuits using the
AOM-MUXF for dual channel applications.
The INX can contain four (4), 50 watt, 25 VRMS AM-50
audio amplifiers, each with two (2), separate speaker cir-
cuits that can be wired Style Y (Class B) or Style Z (Class
A). Each amplifier can produce its own tone or message
independently of other system amplifiers. Thus, an INX
transponder can produce three (3), audio channels simulta-
neously. Each INX transponder can support four (4), AM-
50s as main amplifiers with one (1), AM-50 as a fail-safe
backup amplifier.
The INX transponder receives its power from a PM-9, 9
ampere, filtered, switching power supply providing twenty-
four (24), VDC nominal operating voltage. The PM-9 has
an integral standby battery charger capable of recharging
up to fifty-five (55), A/H batteries. The E3-BB-BC/INX cabi-
net can house up to 18 A/H sized batteries.GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
www.gamewell-fci.com 9020-0613 Rev. C  page 3 of 5
FIRE
FIRE
INX
E3 with
Two (2), notification appliance
Circuits, each rated
2.0 amps. @ 24 VDC
(Power-limited).
Two analog addressable
Signaling line circuits
for 39 devices
(Power-limited)
Style 6 (Class “A”) with
optional
CAOM
INCC-C Command Center with optional
Microphone and Fire Fighter’s Handset
ASM-16 Addressable Switch Modules with
16 Programmable, addressable
Switches, each with three (3), programmable
Indicating LEDs (red, green yellow)
INX Transponder with
six (6), independently
Programmable
speaker circuits, each
Rate 50 watts at
25 VRMS, (Power-limited)
Three simultaneous
Audio channels
up to 16 programmable
voice messages
(Power-limited)
Optional Digital
Alarm Communicator
Transmitter (DACT-E3)
for local or network-
wide event reporting
Twisted-pair or fiber-optic cable
between nodes 3,000 ft. (900m)
distance with wire
up to 8 dB loss with fiber-optic
One signaling line circuit with
16-AOM-TELF and
32 AOM-MUXF addressable
Devices (AOM-TELFs shown)
Style 6 (Class “A”) standard
(Power-limited)
Fire fighter phone riser
(Power-limited)
FIRE FIRE
Gamewell-FCI
Gamewell-FCI
Figure 1GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9020-0613 Rev. C   page 4 of 5 www.gamewell-fci.com
3,000 ft. (7,620 cm)  (max.) between nodes using wire
8 dB loss (max.) between nodes using fiber-optic cable
Initiating / Control Devices
Typical for SLC No. 2
(if used)
NAC
NAC
FIRE
FIRE
One phone riser
One SLC
(16 AOM-TELFs & 32 AOM-MUXFs)
6 Speaker appliance ckts.
150 watts max. @ 25 VRMS
w/ 50 watts standby
One phone riser
NAC
NAC
FIRE
FIRE
Local Annunciators, LCD-7100, (Max. 5)
Global display for all network events if
set to Region “0”
Initiating / Control
Devices Typical for
SLC No. 2 (if used)
One SLC
(16 AOM-TELFs & 32 AOM-MUXFs)
One phone riser
One SLC
(16 AOM-TELFs & 32 AOM-MUXFs)
Optional Integral DACT
Initiating / Control
Devices Typical for
SLC No. 2 (if used)
Local annunciators,
LCD-7100, (Max. 5)
Global display for all network
Events if set to Region “0”
FIRE
Connect if wired
Class A, Style 6 or 7 only
INX INX
Gamewell-FCI
INX
6 Speaker appliance ckts.
150 watts max. @ 25 VRMS
w/ 50 watts standby
6 Speaker appliance ckts.
150 watts max. @ 25 VRMS
w/ 50 watts standby
E3 Series
E3 Series
E3 Series
Gamewell-FCI
Gamewell-FCI Gamewell-FCI
Gamewell-FCI
Gamewell-FCI
Figure 2GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
www.gamewell-fci.com 9020-0613 Rev. C  page 5 of 5
Specifications
Detailed product specifications may be found in:
9020-0542 INCC Intelligent Network Command
Center Datasheet
9020-0637 E3 Series™ Datasheet
9020-0541 INX Intelligent Network Transponder
Datasheet
Ordering Information
E3 Control
Part Number Description
ILI-MB-E3 Intelligent Loop Interface-Main Board
LCD-E3 LCD Keypad Display
PM-9 Power Supply
RPT-E3 Network Repeater
DACT-E3 Digital Alarm Communicator Transmitter
LCD-7100
(Optional)
Remote Serial LCD Display
INCC Intelligent Network Command Center
Part Number Description
INI-VGC Command Center Voice Gateway
INI-VGC-UTP Voice Gateway for unshielded twisted-pair
wire only
ASM-16 Programmable Switch Module
(occupies single slot of inner door)
NGA Network Graphic Annunciator
ANU-48 Remote LED Driver
INCC-IDT Inner door w/one double slot for INCC-
TEL fire fighter handset and 4 single slots
INCC-ID Inner door w/6 single slots
INCC-CABR INCC backbox (black) with red outer door,
19” H x 19” W x 4” D (48 x 48 x 10 cm)
Ordering Information (Continued)
Optional Accessories
Part Number Description
INCC-TEL Fire Fighter Telephone Handset
(requires INCC-IDT Inner Door)
INCC-MIC Paging Microphone Module
(occupies one single slot of Inner Door)
INCC-BP Command Center Blank Face Plate
(occupies one single slot of Inner Door)
INX Intelligent Network Transponder
Part Number Description
INX-VGX Transponder Voice Gateway
PM-9 INX 9 ampere Power Supply
AM 50 INX 50 Watt amplifier
INX-CAB INX 19” x 19” x 4” (48 x 48 x 10 cm)
Backbox with Black Door
INX-CABR INX 19” x 19” x 4” (48 x 48 x 10 cm)
Backbox with Red Door
For additional information on the cabinets, refer to the E3
Series™ Cabinets data sheet (Part Number: 9020-0649).NON-CODED, MANUAL
FIRE ALARM STATIONS
MS SERIES
Specifications are provided for information only,  are
not intended to be used for installation purposes and
are believed to be accurate.  However, no responsi-
bility is assumed by Gamewell-FCI for their use.
Specifications subject to change without notice.
© 2006                                    All Rights Reserved.
www.gamewell.fci.com
9020-0358 Rev. I Page 1of 2
An ISO 9001 Company
Model MS-2, MS-2H
The MS-2 manual fire alarm stations are
dual action devices.  These stations re-
quire that the outer door be lifted to ex-
pose the actuation door which is then
pulled forward to operate the alarm toggle
switch. The actuation door is now locked
in the readily observable “alarm” position.
To reset the station, a key (common to
FCI control panels) must be inserted and
turned ¼ turn clockwise, opening the
station. Closing the station resets the
switch automatically.
An optional breakglass rod is available
for positive indication of station operation.
Model MS-2L (Institutional)
Operation of the Model MS-2L institu-
tional station requires that a special key
be used to release the actuation door
before it can be operated.
Model MS-2-D (Multiple Contact)
The MS-2-D features a DPST switch for
multiple signaling via wire lead connec-
tions.
Model MS-6 (Single Action)
The MS-6 station is a single action de-
vice, requiring only the pulling of the ac-
tion door to release the compressed but-
ton switch.   It is available either with ter-
minals (MS-6T) or wire leads (MS-6).
The station resets in the same
manner as the MS-2.  The reset key is
common to FCI control panels.
MS-2
MS-2H
MS-6
FEATURES
•  Single and Dual Action Versions
• Tumbler Lock for Test and Reset
   Keyed Alike with FCI Control Panels
• Rugged Metal Construction
• Positive Indication of Operation
over 180° Viewing Angle
• Surface or Semi-flush Mounting
• Shock and Vibration Resistant
• Institutional  Version (MS-2L)
• Optional “FIRE SUPPRESSION
   SYSTEM RELEASE” Markings
   (MS-2H)
• Optional DPST Switch (MS-2-D)MS SERIES
 9020-0358 Rev. I    Page 2 of 2
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118
www.gamewell.fci.com
Specifications are provided for information only,  are not intended to be used for installation purposes and are believed to be accurate.
However, no responsibility is assumed by Gamewell-FCI, for their use.  Specifications subject to change without notice. © 2006 All Rights Reserved
AGENCY APPROVALS
UL (Std 38)
FM  (MS-2)
      (MS-6, MS-6T)
C.S.F.M.
NYC-BS&A (MS-2)
NYC-MEA  (MS-6)
File S2465
OJ3A9.AY/12880
1D4A7.AY
7150-0694:107
960-81-SA
103-93-E
Extruded 6063/T5 aluminium
Clear anodize
Enclosed toggle
Enclosed push button
Silver plated bronze or copper
6 amp. max. @ 30 VDC (resistive)
0.5 amp. max. @ 30 VDC (resistive)
5” H x 3.4” W x 2.8” D (12.7 cm x 8.64 cm x 7.11 cm)
SPECIFICATIONS
Material (MS-2, MS-6)
Doors (MS-2, MS-6)
Switch Type
      MS-2
      MS-6
Contact Material
Contact Ratings
      MS-2
      MS-6
Dimensions (overall)
      MS-2, MS-6
ORDERING INFORMATION
Part No.
1100-0615
1100-0634
1100-0621
1100-0617
1100-0632
1100-0633
2520-0023
1120-0206
Model
MS-2
MS-2H
MS-2L
MS-2-D
MS-6
MS-6T
BB-2
Description
Dual action fire alarm station
Dual action station with
 “FIRE SUPPRESSION SYSTEM RELEASE” markings
Institutional fire alarm station
Dual action station with DPST switch
Single action station, wire leads
Single action station, terminals
Surface back box for MS-2, MS-6 stations
Package of two replacement breakglass rods for MS-2 stationGAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2008 Gamewell-FCI.   All rights reserved.  www.gamewell-fci.com  9020-0626 Rev. C1  page 1 of 1
Description
 
The Gamewell-FCI Velociti
® Series, addressable monitor
module AMM-2F is a single Style B, Class B initiating
device circuit (IDC) with a 47KW end-of-line resistor. This  
module provides an address for any device or group of
devices connected to this circuit on the signaling line
circuit (SLC) of the Gamewell-FCI addressable series fire
alarm control panel. Any initiating device with normally
open (N.O.) dry contacts may be made addressable
when connected to the AMM-2F module.
 
The Velociti
® Series use a communication protocol that
substantially increases the speed of communication  
between the sensors and certain Gamewell-FCI analog
addressable fire alarm controls. These devices operate
in a grouped fashion. If one of the devices in the group
has a status change, the panel’s microprocessor stops
the group poll and concentrates on the single device.
The net effect is response speed up to five times greater
than earlier designs.
 
The AMM-2F module can be programmed to provide a
wide variety of input functions to the Gamewell-FCI ad-
dressable series fire alarm control panels. It can be iden-
tified as a manual station, heat detector, plenum detec-
tor, waterflow switch, tamper switch, N.O. contact, smoke
detector, projected beam smoke detector, sub loop,  
remote zone, etc. It can also serve as a remote system
silence, system reset, system acknowledge or drill
switch. It is even possible to customize its device type to
meet specific job requirements.  
 
The initiating device circuit of the AMM-2F can support a
maximum line resistance of up to 40 ohms allowing the
use of linear heat detection devices. The compact size
facilitates the installation of the module inside manual
stations, or mounting boxes of various types of alarm
initiating devices.
 
 
Velociti
® and E3 Series®
are registered trademarks of Honeywell  
International Inc.
Addressable
Monitor Module
AMM-2F
 
Features
 
•  Compact size allows easy installation
• Class B, Style B, initiating circuit
•  40 Ohm line resistance for each initiating device  
 circuit
• Connects to any normally open dry contact device
•  Bicolor LEDs flash green whenever the module
 is addressed, and light steady red on alarm*
*Note: Only the red LED is operative in panels that do not  
operate in Velociti
® mode.
 
Specifications
 
Supervisory current:  .000375 amps.
Alarm current:  .00060 amps.
Operating temperature:  32˚ to 120˚ F (0˚ to 49˚ C)
Relative humidity:  10 to 93% (non-condensing)
End-of-line Resistance:  47K ohms
Dimensions:  1.3” L x 2.5” W x 0.5” D
(3.3 x 6.4 x 1.3 cm)
Ordering Information
 
Model  Description
AMM-2F  Addressable monitor module, single circuit,
Style B, Class B
 
An ISO 9001-2000 Company
 Conventional Duct   CS-2056   09/01/06 Page 1 of 2
Description
The Gamewell conventional duct
smoke detectors provide early detec-
tion of smoke and products of combus-
tion present in air moving through an
HVAC duct. These devices are de-
signed for prevention of smoke recircu-
lation by the air handling systems.
Fans, blowers and complete systems
may be shut down, or activated into
fire mode operation in the event of
smoke detection.
The Gamewell Duct Smoke Detector may use a photoelectric, or ionization
detector head. A visual alarm indicator is mounted on the housing front for sta-
tus indication. A manual reset switch is provided on the front of the detector.
Air sampling is accomplished by two tubes which protrude into the duct. An
exhaust tube of one standard length of 7.5" (19.05 cm) is provided with the
detector housing. Intake sampling tubes, which must be ordered separately, are
supplied in three standard lengths: 2.5, 5.0, or 10.0 feet (0.76, 1.524 or 3.048
m).
Standard features of the duct type smoke detectors include a local red LED
alarm indicator, local functional test/reset capability, provisions for remote test,
remote alarm indication, and connections for remote reset switch.
Engineer’s Specifications
Duct smoke detectors shall be the Gamewell series: for two-wire or four-wire
24 VDC operation use model 30954 (ionization) or 30955 (photoelectric); univer-
sal voltage models are 70957-01 (ionization) or 70958-01 (photoelectric). The
detectors shall be Listed by Underwriters Laboratories per UL 268A. The detec-
tors shall operate at air velocities from 300 to 4,000 feet (31.44 to 1219.2 m) per
minute.
The duct detector housing shall have a metal chassis with a plastic cover, and
mechanical installation may be performed without removal of the detector cover.
Visual indication of alarm must be provided on the detector front mounted at a
30°   
slant to provide a wide viewing angle. A manual reset/test switch shall be
located on the front of the device.
Detector heads shall not require additional filters, or screens which must be
maintained. The housing shall contain a detector base which will accept photo-
electric or ionization heads. Terminal connections shall be of the screw type
and be a minimum of a #6 screw. Terminals shall be provided for remote alarm
indication and remote reset/test switches. All wiring must comply with local
codes and regulations.
Wiring Diagram
Features
• Photoelectric or Ionization.
• Two form-c alarm contacts.
• Remote reset and test.
• 24 VDC or universal input
models.
• Remote alarm LED.
• Form-C trouble contact.
• Two or four-wire operation.
• Mounting template and hardware
provided.
Listings
Listings and approvals below
apply to the basic Conventional
Duct Smoke Detectors. In some
cases, certain modules may not
be listed by certain approval
agencies, or listing may be in
process. Consult factory for
latest listing status.
• UL Listed:
Conventional Duct
Smoke Detectors
g2056phl.jp gConventional Duct   CS-2056    09/01/06 Page 2 of 2
Specifications and wiring information are provided for information only and are
believed to be accurate. Gamewell-FCI assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring
instructions shipped with the product shall always be used for actual installation. For
more information, contact Gamewell-FCI.
Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
Phone: 203-484-7161
Fax: 203-484-7118
www.gamewell-fci.com
A Honeywell Company
© 2006 Gamewell-FCI
Ordering Information
30954 Ionization smoke detector for air duct, 2-wire or 4-wire,
24 VDC (2650-560).
30955 Photoelectric smoke detector for air duct, 2-wire or
4-wire, 24 VDC (2650-561).
GW-30203-01 Remote LED alarm indicator, 2 VDC, for models
30954 and 30955.
GW-30007-01 Remote test station, for models 30954 and 30955.
GW-30069 End-of-line relay for power supervision, 24 VDC, for
models 30954 and 30955.
GW-70957-01 Ionization duct smoke detector, universal voltage 110
VAC, 24 VAC, 24 VDC, (RWH-N).
GW-70958-01 Photoelectric duct smoke detector, universal voltage
110 VAC, 24 VAC, 24 VDC, (RWH-P).
GW-30203 Remote LED alarm indicator, 24 VDC, for models
70957-01 and 70958-01.
GW-30003 Remote test station for models 70957-01 and 70958-01.
GW-70896-02 Sampling tube, 2.5 ft. (0.762 m).
GW-70896-05 Sampling tube, 5.0 ft. (1.524 m).
GW-70896-10 Sampling tube, 10.0 ft. (3.048 m).
GW-71034 Ionization detector head replacement.
GW-72247 Duct detector enclosure (WP-1) (see CS-2308).
Specifications
Ambient temperature
30°F to 120°F (0°C to 49°C).
Humidity
10% to 85% relative humidity.
Material
16-gauge steel back-box. Plastic
ABS-640V0 cover.
Finish
Textured grey finish with clear
cover.
Dimensions
10.0" H x 8.25" W x 2.25" D
(cm: 25.4 H x 21.0 W x 5.7 D).
Maximum net weight
4.0 lbs. (1.814 kg).
Radioactive element
For ionization versions only:
americium 241 (1.0 microcuries).
Air velocity
300 to 400 feet (m: 91.44 to
121.92) per minute.
Pressure differential
0.01 – 1.2 inches (cm: 0.01 –
3.048) of water.
Power requirements
Model 30954 and 30955: 24 VDC
operation at 0.00005 A standby,
0.05 A alarm.
Model 70957-01 and 70958-01:
115 VAC operation at 0.02 A
standby, 0.035 A alarm; 24 VAC
operation at 0.061 standby, 0.16
A alarm; 24 VDC operation at
0.025 A standby, 0.07 A alarm.
Relay contact rating
Model 30954 and 30955: alarm
contacts, two Form-C: rated at
1.0 amp, 30 VDC.
Model 70957-01 and 70958-01:
alarm contacts, two Form-C
rated at 10.0 A at 115 VAC
resistive; trouble contacts, one
Form-C rated 4.0 amps at 115
VAC resistive.Remote Annunciator
Features
 
• Two-line 16-character LCD display.
 
• Indicates trouble, alarm, supervisory
and system status conditions with
LEDs and LCD display.
 
• Each RAN-400 is individually  
supervised by the FLEX-410 FACP.
 
• Up to four per FLEX-410 FACP.
 
• Operation and appearance compara-
ble to the control panel’s on-board  
annunciator.
 
• Can be wired up to 1500 ft. (457.20 m)
from FACP.
 
 
Specifications
Operating voltage
 24 VDC.
Current draw
 Standby: 30 mA.
 Alarm: 50 mA.
Dimensions
 Width: 7.188” (18.26 cm).
 Height: 5.0” ( 12.7 cm).
 Depth: 1.125” (2.86 cm).
 
Listings
 
Operating temperature
 32° to 120°F (0° to 49°C).
 
Maximum wiring distance
 1500 ft. (457.20 m).
 Listings and approvals below apply to
the basic RAN-400. In some cases,  
certain modules may not be listed by
certain approval agencies, or listing
may be in process. Consult factory for
latest listing status.
 
• UL Listed: file S521.
 
Description
The RAN-400 is the remote annunciator for the Flex 410 Fire Alarm
Control Panel (FACP). The RAN-400 performs all system operations. It
also provides trouble and alarm information, and can be used for pro-
gramming.
 
Operation
When the system is normal and receiving AC power, the power LED is
on and all other LEDs are off. Other LEDs turn on as the conditions
occur.
 
Users identify themselves to the control panel by entering a code on
the annunciator. When a user presses a button, the annunciator piezo
beeps and the LCD prompts the user to enter a code or other relevant
information.
 
Multiple users can work at different annunciators simultaneously with-
out affecting each other.
 
Engineer’s Specifications
The contractor shall furnish and install where indicated on the plans,
the RAN-400 Remote Annunciator. Module shall be of a LCD type with
a 2 x 16 display. Module shall be capable of remote programming as
well as providing alarm, trouble information along with resetting of
alarms and silencing of trouble and alarm conditions. Module ID shall
be programmed with a four position DIP. The control shall be capable
of supporting up to four supervised RAN-400. Module shall be de-
signed to mount on a dual-gang electrical box with 18 AWG (0.821
mm²) to 14 AWG (2.08 mm²) wire.
 
Ordering Information  
RAN-400 Remote annunciator for FLEX-410 FACP.
   
   
  RAN-400 CS-2486  09/01/06  Page 1 of 2
g2486c1.wmf Specifications and wiring information are provided for information only and are be-
lieved to be accurate. Gamewell-FCI assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring instruc-
tions shipped with the product shall always be used for actual installation. For more
information, contact Gamewell-FCI.
 
Page 2 of 2     Ran-400  CS-2486    09/01/06
 
 
 
 
 
 
Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
Phone: 203-484-7161
Fax: 203-484-7118
www.gamewell-fci.com
 
A Honeywell Company
© 2006 Gamewell-FCI GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2009 by Honeywell International Inc.   All rights reserved. www.gamewell-fci.com CS-2513 Rev. A page 1 of 2
i ii i
3 Series Detectors  Series Detectors  Series Detectors  Series Detectors
Intelligent Conventional
Smoke Detector Series
Description
The System Sensor, i
3 Series smoke detectors rep-
resent a significant advancement in conventional
detection. The i
3 family is founded on three princi-
ples: installation ease, intelligence, and instant
inspection.
The i
3 Series redefines installation ease with its plug-
in design. This design allows an installer to pre-wire
the bases included with the heads. The large wire
entry port and in-line terminals provide ample room
for neatly routing the wiring inside the base. The
base accommodates a variety of back box mounting
methods as well as direct mounting with drywall
anchors. To complete the installation, i
3 heads plug-
in to the base.
i
3 detectors offer a number of intelligent features to
simplify testing and maintenance. Drift compensa-
tion and smoothing algorithms are standard with the
i
3 line, to minimize nuisance alarms. When the i
3 is
connected to the 2W-MOD loop test/maintenance
module or an i
3 ready panel (MS-2 and MS-4)
equipped with the i
3 protocol, 2-wire i
3 detectors are
capable of generating a remote maintenance signal
indicating when they are in need of cleaning. This
signal is indicated via an LED located at the module
and/or the panel. To read the sensitivity of i
3 detec-
tors, the SENS-RDR is a wireless device that dis-
plays the sensitivity in terms of percent per foot
obscuration.
The i
3 Series provides wide angle red and green
LED indicators for instant inspection of the detector
condition, indicating: normal standby, out-of-sensitiv-
ity, alarm, or freeze trouble conditions. When the i
3 is
connected to the 2W-MOD loop test/maintenance
module or an i
3 ready panel (MS-2 and MS-4) with
the i
3 protocol, the EZ Walk loop test feature is avail-
able on 2-wire i
3 detectors. This feature verifies the
initiating loop wiring by providing LED status indica-
tion at each detector.
Features
• Built-in remote maintenance signaling
• Drift compensation and smoothing algorithms
• Stop-Drop ‘N Lock attachment to base
• Simplified sensitivity measurement
• Plug-in detector line - mounting base included
• Large wire entry port
• In-line terminals with SEMS screws
• Mounts to octagonal and single-gang back-
boxes, 4” (10.16 cm) square backboxes, or direct
to ceiling
• Removable detector cover and chamber to
simplify cleaning
• Wide angle, dual color LED indication
• Loop testing via EZ Walk feature
• Built-in test switch
i
3
An ISO 9000-2000 Company
APPROVED
FM
SIGNALING
S911
MEA Approved
7272-1209:210 GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
CS-2513 Rev. A   page 2 of 2 www.gamewell-fci.com
Specifications Ordering Information
Operating Voltage:      12/24 VDC (peak)
Standby Current: 2-wire: 50 ìA maximum average
4-wire: 50 ìA maximum average
Maximum Alarm
Current: 2-wire: 130 mA limited by             
control panel
4-wire: 20 mA @ 12 V,
23 mA @ 24V
Alarm Contact
Ratings: 2-wire: n/a
4-wire: 0.5 A @ 30 V AC/DC
Operating
Temperature Range:
  2W-B and 4W-B: 32°F – 120°F (0°C – 49°C)
  2WT-B and 4WT-B: 32°F – 100°F (0°C – 37.8°C)
Operating
Humidity Range: 0% to 95% RH non-condensing
Thermal Sensor: 135°F (57.2°C) fixed
Freeze Trouble: 2WT-B and 4WT-B only:
41°F (5°C)
Sensitivity: 2.5% /ft. nominal
Input Terminals: 14 – 22 AWG
Dimensions
(including base): 5.3 inches (127 mm) diameter,
2.0 inches (51 mm) height
Weight: 6.3 oz. (178 grams)
Mounting: 3.5-inch (8.8 cm) octagonal
backbox
4-inch (10.16 cm) octagonal
backbox
Single-gang back box
4-inch (10.16 cm) square backbox
with plaster ring
Direct mount to ceiling
Model ThermalWiring Alarm Current
2W-B No 2-wire 130 mA max. limited by control
 panel
2WT-B Yes 2-wire 130 mA max. limited by control
panel
4W-B No 4-wire 20 mA @ 12V, 23mA @24V
4WT-B Yes 4-wire 20 mA @ 12V, 23mA @24V
2WTA-B Yes 2-wire 130 mA max. limited by control
panel
2WTR-B Yes 2-wire 130 mA max. limited by control
panel
4WTA-B Yes 4-wire 35 mA
4WTR-B Yes 4-wire 35 mA
4WTAR-B Yes 4-wire 50 mA
4WITAR-B Yes 4-wire 50 mA
Model Description
2W-MOD 2-wire loop test/maintenance module
SENS-RDR
RT Removal / replacement tool
A77-AB2 Retrofit adapter bracket
CRRS-MODA Reversing relay/synchronization
module
CSENS-RDRA Sensitivity readerGAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2006 Honeywell International Inc.   All rights reserved. www.gamewell-fci.com CS-2539 Rev. A  page 1 of 4
Selectable Output
Notification Appliances
Description
SpectrAlert
® Advance selectable-output horns, strobes and
horn/strobes are rich with features guaranteed to decrease
installation times and maximize profits. The SpectrAlert
Advance series of notification appliances is designed to
simplify your installations, with features such as: plug-in
designs, instant feedback messages to ensure correct
installation of individual devices, and eleven (11), field-
selectable candela settings for wall, ceiling strobes and
horn/strobes.
More specifically, when installing Advance products, first
attach a universal mounting plate to a four-inch square,
four-inch octagon, or double-gang junction box. The two-
wire mounting plate attaches to a single-gang junction box.
Then, connect the notification appliance circuit wiring to the
SEMS terminals on the mounting plate.
Finally, attach the horn, strobe, or horn/strobe to the
mounting plate by inserting the product’s tabs in the mount-
ing plate’s grooves. The device will rotate into position,
locking the product’s pins into the mounting plate’s termi-
nals. The device will temporarily hold in place with a catch
until it is secured with a captured mounting screw.
SpectrAlert Advance products offer the following
options:
• 12 or 24 volts.
• At 24 volts, 15, 15/75, 30, 75, 95, 110, 115, 135, 150,
177, or 185 candela by way of rear-mounted slide
switch and front viewing window.
• Horn tones and volume by way of rotary switch.
The SpectrAlert Advance series includes outdoor notifica-
tion appliances. Outdoor strobes and horn/strobes (two-
wire and four-wire) are available for wall or ceiling. Outdoor
horns are available for wall only. All System Sensor out-
door products are rated between –40°F and 151°F (–40°C
and 66°C) in wet or dry applications.
Sync•Circuit™ is a trademark, and SpectrAlert® and System Sensor® are registered trade-
marks of Honeywell International Inc. ©2006 by ADT. All rights reserved. Unauthorized use
of this document is strictly prohibited.
Features
• Plug-in design.
• Same mounting plate for wall- and ceiling-mount units.
• Shorting spring on mounting plate for continuity check
before installation.
• Captive mounting screw.
• Tamper-resistance capability.
• Field-selectable candela settings on wall or ceiling units:
15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, 185.
• Automatic selection of 12 or 24 volt operation at 15 and
15/75 candela.
• Outdoor wall and ceiling products.
• Outdoor products rated from –40°F and 151°F
(–40°C and 66°C).
• Minimal intrusion into the backbox.
• Horn rated at 88+ dbA at 16 volts.
• Rotary switch for tone selection.
• Three horn volume settings.
• Electrically compatible with SpectrAlert
® products.
7087pho1.jpg
Indoor Ceiling Horn/Strobe Outdoor Ceiling Strobe
7087pho2.jpg 7087pho3.jpg
Indoor Wall Horn/Strobe
7087pho4.jpg
Indoor Ceiling Strobe Indoor Wall Horn
7087pho5.jpg
Outdoor Wall Strobe
7087pho6.jpg
An ISO 9000-2000 Company
7125-1653:188
SIGNALING
MEA Approved
452-05-E S4011GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
CS-2539 Rev. A   page 2 of 4 www.gamewell-fci.com
Models available:
• Indoor wall-mount: horn, strobe, 2-wire horn/strobe,
4-wire horn/strobe.
• Indoor ceiling-mount: strobe, 2-wire horn/strobe,
4-wire horn/strobe.
• Outdoor wall-mount: horn, strobe, 2-wire horn/strobe,
4-wire horn/strobe.
• Outdoor ceiling-mount: strobe, 2-wire horn/strobe,
4-wire horn/strobe.
Engineering Specifications
SpectrAlert Advance horns, strobes, and horn/strobes shall
mount on a standard 4.0" x 4.0" x 1.5" (10.16 x 10.16 x 3.81 cm)
backbox, 4.0"  (10.16 cm) octagonal backbox, or a double-
gang backbox. Two-wire products shall also mount on a
single-gang 2.0" x 4.0" x 1.875" (5.08 x 10.16 x 4.763 cm) back-
box. A universal mounting plate shall be used for mounting
ceiling and wall products. The notification appliance circuit
wiring shall terminate at the universal mounting plate. Also,
SpectrAlert Advance products, when used with the
Sync•Circuit™ Module accessory, shall be powered from a
non-coded notification appliance circuit output and shall
operate on a nominal 12 or 24 volts. When used with the
Sync•Circuit Module, 12-volt rated notification appliance
circuit outputs shall operate between 9 and 17.5 volts; 24-
volt rated notification appliance circuit outputs shall operate
between 17 and 33 volts. Indoor SpectrAlert Advance prod-
ucts shall operate between 32°F and 120°F (0°C and 49°C)
from a regulated DC, or full-wave-rectified, unfiltered power
supply. Strobes and horn/strobes shall have field-select-
able candela settings including 15, 15/75, 30, 75, 95, 110,
115, 135, 150, 177, 185.
Strobe
The strobe shall be a System Sensor SpectrAlert Advance
Model _______ Listed to UL STD 1971 and shall be
approved for fire protective service. The strobe shall be
wired as a primary-signaling notification appliance and
comply with the Americans with Disabilities Act require-
ments for visible signaling appliances, flashing at 1 Hz over
the strobe’s entire operating voltage range. The strobe light
shall consist of a xenon flash tube and associated lens/
reflector system.
Horn/Strobe Combination
The horn/strobe shall be a System Sensor SpectrAlert
Advance Model _______ Listed to UL Standards 1971 and
464 and shall be approved for fire protective service. The
horn/strobe shall be wired as a primary-signaling notifica-
tion appliance and comply with the Americans with Disabil-
ities Act requirements for visible signaling appliances,
flashing at 1 Hz over the strobe’s entire operating voltage
range. The strobe light shall consist of a xenon flash tube
and associated lens/reflector system. The horn shall have
three audibility options and an option to switch between a
Temporal 3 pattern and a Non-Temporal (continuous) pat-
tern. These options are set by a multiple position switch.
On four-wire products, the strobe shall be powered inde-
pendently of the sounder. The horn on horn/strobe models
shall operate on a coded or non-coded power supply.
Outdoor Products
SpectrAlert Advance outdoor horns, strobes and horn/
strobes shall be listed for outdoor use by UL and shall
operate between –40°F and 151°F (–40°C and 66°C). The
products shall be listed for use with a System Sensor out-
door/weatherproof backbox with half-inch and three-
fourths-inch conduit entries.
Synchronization Module
The module shall be a System Sensor Sync•Circuit
_______ Listed to UL STD 464 and shall be approved for
fire protective service. The module shall synchronize Spec-
trAlert strobes at 1 Hz and horns at Temporal 3. Also, while
operating the strobes, the module shall silence the horns
on horn/strobe models over a single pair of wires. The
module shall mount to a 4.688" x 4.688" x 2.125"  (11.906 x
11.906 x 5.398 cm) backbox. The module shall also control
two Style Y (Class B) circuits or one Style Z (Class A) cir-
cuit. The module shall synchronize multiple zones. Daisy-
chaining two or more synchronization modules together will
synchronize all the zones the modules control. The module
shall not operate on a coded power supply.GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
www.gamewell-fci.com CS-2539 Rev. A  page 3 of 4
Strobe Current Draw,
UL Maximum (mA RMS)
Horn Current Draw,
UL Maximum (mA RMS)
Horn and Horn/Strobe
Rotary Switch Setting)
Horn and Horn/Strobe Output (dBA)
Operating Specifications
Standard operating
temperature: 32° F to 120° F (0° C to 49° C)
K Series operating
temperature: -40° F and 151° F
(-40° C and 66° C)
Humidity range: 10% to 93% non-condensing
(indoor products).
Strobe flash rate: 1 flash per second.
Nominal voltage: regulated 12 VDC/FWR or regu-
lated 24 VDC.FWR.
Note: Full Wave Recitified (FWR)
voltage is a non-regulated, time-
varying power source that is used
on some power supply and panel
outputs.                                               
Operating voltage
range: 8 V to 17.5 V (12 V nominal); or 16
V to 33 V (24 V nominal).
Note: P, S, PC, and SC products
will operate at 12 V nominal only for
15 cd and 15/75 cd.
Input terminal wire
gauge: 12 to 18 AWG (3.31 to 0.821 mm2).
Ceiling-mount
dimensions
(including lens): 6.8” diameter x 2.5” deep
(17.3 diameter x 6.4 deep cm)
Wall-mount
dimensions
(including lens): 5.6” H x 4.7” W x 2.5” D
(14.2 H x 11.9 W x 6.4 D cm)
Horn dimensions: 5.6” H x 4.7” W x 1.3” D
(14.2 H x 11.9 W x 3.3 D cm)
     8 - 17.5 V     16 - 33 V     
Candela        DC      FWR      DC       FWR   
Standard
Candela
 Range           
15 123 128 66 71
15/75  142 148 77 81
30 NA NA 94 96
75 NA NA 158 153
95 NA NA 181 176
110 NA NA 202 195
115 NA NA 210 205
High
Candela
Range
135 NA NA 228 207
150 NA NA 246 220
177 NA NA 281 251
185 NA NA 286 258
Sound
     Pattern dB
     8 - 17.5 V        16 - 33 V
DC FWR DC FWR
Temporal  High 57 55 69 75
Temporal  Medium 44 49 58 69
Temporal Low 38 44 44 48
Non-temporal High 57 56 69 75
Non-temporal Medium 42 50 60 69
Non-temporal Low 41 44 50 50
Coded High 57 55 69 75
Coded Medium 44 51 56 69
Coded Low 40 46 52 50
Setting Repetition Rate dB Level
1 Temporal Horn High
2 Temporal horn Medium
3 Temporal horn Low
4 Normal horn Low
5 Normal horn Medium
6 Normal horn Low
7* Externally coded       High
8* Externally coded    Medium          
9* Externally coded     Low
*NOTE: Settings 7, 8 and 9 are not available on 2-wire
horn/strobe
Switch
Position
Sound
Pattern dB
8 - 17.5 V 16 - 33 V
DC   FWR DC FWR
1 Temporal High 78 78 84 84
2 Temporal Medium 74 74 80 80
3 Temporal Low 71 73 76 76
4 Non-temporal High 82 82 88 88
5 Non-temporal Medium 78 78 85 85
6 Non-temporal Low 75 75 81 81
7* Coded High 82 82 88 88
8* Coded Medium 78 78 85 85
9* Coded Low 75 75 81 81
*NOTE: Settings 7, 8, and 9 are not available on 2-wire
horn/strobe.GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
CS-2539 Rev. A   page 4 of 4 www.gamewell-fci.com
Two-Wire Horn/Strobe, STANDARD Candela Range (15 - 115 cd),
UL Maximum Current Draw (mA RMS)
Input, Sound Pattern, dB Level
8 - 17.5 V 16 - 33 V
15 15/75 15 15/75 30 75 95 1101 115
DC Input, Temporal High 137 147 79 90 107 176 194 212 218
DC Input, Temporal, Medium 132 144 69 80 97 157 182 201 210
DC Input, Temporal, Low 132 143 66 77 93 154 179 198 207
DC Input, Non-temporal, High 141 152 91 100 116 176 201 221 229
FWR Input, Non-temporal Medium            133 145 75 85 102 163 187 207 216
DC Input, Non-temporal, Low 131 144 68 79 96 156 182 201 210
FWR Input, Temporal, High 136 155 88 97 112 168 190 210 218
FWR Input, Temporal, Medium 129 152 78 88 103 160 184 202 206
FWR Input, Temporal, Low 129 151 76 86 101 160 184 194 201
FWR Input, Non-temporal, High 142 161 103 112 126 181 203 221 229
FWR Input, Non-temporal, Medium 134 155 85 95 110 166 189 208 216
FWR Input, Non-temporal, Low 132 154 80 90 105 161 184 202 211
Two-Wire Horn/Strobe, HIGH Candela Range (135 - 185 cd),
UL Maximum Current Draw (mA RMS
DC Input
16 - 33 V 16 - 33 V
135 150 177 185 FWR Input 135 150 177 185
DC, Temporal High 245 259 290 297 FWR, Temporal, High 215 231 258 265
DC, Temporal Medium 235 253 288 297 FWR, Temporal, Medium 209 224 250 258
DC, Temporal Low 232 251 282 292 FWR, Temporal, Low 207 221 248 256
DC, Non-temporal, High 255 270 303 309 FWR, Non-temporal, High 233 248 275 281
DC, Non-temporal, Medium 242 259 293 299 FWR, Non-temporal, Medium 219 232 262 267
DC, Non-temporal, Low 238 254 291 295 FWR, Non-temporal, Low 214 229 256 262
Ordering Information:
Model Description Model Description
WALL HORNS/STROBES CEILING HORN/STROBES
P2R 2-wire horn/strobe, standard cd, red. PC2R 2-wire horn/strobe, standard cd, red.
P2RH 2-wire horn/strobe, high cd, red. PC2RH 2-wire horn/strobe, high cd, red.
P2RK 2-wire horn/strobe, standard cd, red, outdoor. PC2RK 2-wire horn/strobe, standard cd, red, outdoor.
P2RHK 2-wire horn/strobe, high cd, red, outdoor. PC2RHK 2-wire horn/strobe, high cd, red, outdoor.
P2W 2-wire horn/strobe, high cd, white. PC2W 2-wire horn/strobe, standard cd, white.
P2WH 2-wire horn/strobe, high cd, white. PC2WH 2-wire horn/strobe, high cd, white.
P4R 4-wire horn/strobe, standard cd, red. PC4R 4-wire horn/strobe, standard cd, red.
P4RH 4-wire horn/strobe, high cd, red. PC4RH 4-wire horn/strobe, high cd, red.
P4RK 4-wire horn/strobe, standard PC4RK 4-wire  horn/strobe, standard cd, red, outdoor.    
P4RHK 4-wire horn/strobe, high cd, red, outdoor. PC4RHK 4-wire horn/strobe, high cd, red, outdoor.
P4W 4-wire horn/strobe, standard cd, white. PC4W 4-wire horn/strobe, standard cd, white.
P4WH 4-wire horn/strobe, high cd, white PC4WH 4-wire horn/strobe, high cd, white.
WALL STROBES CEILING STROBES
SR Strobe, standard cd, red. SCR Strobe, standard cd, red.
SRH Strobe, high cd, red. SCRH Strobe, high cd, red.
SRK Strobe, standard cd, red, outdoor. SCRK Strobe, standard cd, red, outdoor.
SRHK Strobe, high cd, red, outdoor. SCRHK Strobe, high cd, red, outdoor.
SW Strobe, standard cd, white. SCW Strobe, standard cd, white.
SWH Strobe, high cd, white. SCHW Strobe, high cd, white.
ACCESSORIES HORNS
BBS-2 Backbox skirt, wall, red. HR Horn, red.
BBSW-2 Backbox skirt, wall, white. HRK Horn, red, outdoor.
BBSC-2 Backbox skirt, ceiling, red. HW Horn, white
BBSCW-2 Backbox skirt, ceiling, white.
NOTE: “High cd” refers to strobes that include 135, 150, 177, and 185 candela settings. “Standard cd” refers to strobes that include
15, 15/75, 30, 75, 95, 110, and 115 candela settings.